Greyline MFS100
Microphone Flow Switch
Standard features include:
- sensor - strap-on, acoustic
- sensor cable - 5ft / 1.5m shielded coaxial
- enclosure - watertight NEMA4X (IP67) polycarbonate
- 1 relay - 5 amp SPDT
- indication - power and relay condition LED's
- sensitivity - adjustable
- power input - 120VAC 50/60Hz
- 1 manual - Installation and Operation
MICROPHONE FLOW SWITCH SPECIFICATIONS
SCOPE: This specification covers a non-intrusive, acoustic
flow switch as manufactured by Greyline Instruments Inc., Massena
New York / Long Sault, Ontario. The instrument shall provide for
flow/no flow control of liquids or solids.
A. PERFORMANCE SPECIFICATIONS
- The flow switch shall operate with a strap-on flow sensor
mounted externally on any sound conductive pipe material
including carbon steel, stainless steel, ductile iron,
copper, FRP, PVC, ABS, or cement lined pipe.
- The Flow Switch shall react to flow noise generated by
the movement of a fluid or solid. ON/OFF control
set-points shall be adjustable by means of a Sensitivity
pot on the face of the instrument.
B. FLOW SENSOR/MICROPHONE
- The flow sensor shall incorporate an acoustic microphone
in a stainless steel housing. It shall be installed on
the outside of a pipe without interrupting flow.
- The flow sensor shall be capable of continuous operation
at temperatures from -5° to 140°F (-20° to 60°C).
- The flow Sensor shall mount on any pipe size from
1/2" to 180" (15mm to 4.5 m), or any pneumatic
conveying system or chute.
- Shall include 5 ft (1.5m) shielded coaxial cable with
waterproof, potted bond to the Sensor head.
- Shall be capable of extending sensor cable up to 20 ft (6
m), without adjustment, and with no reduction in
performance or signal strength.
C. ELECTRONICS/CONTROLLER
- Shall include one 5 ampere SPDT control relay with
adjustable ON/OFF set point.
- Shall be housed in a wall-mount watertight, dust tight
NEMA4X (IP66) fiberglass enclosure with a gasket shatter
proof window.
- The controller shall include dial adjustment for
Sensitivity/Flow set-point.
- The controller shall include a LED light to indicate
relay status, and a separate LED to indicate power ON.
- The flow switch electronics/controller shall operate at
temperatures from -10° to 140°F (-23° to 60°C).
- Power input and Relay connections shall be by screw-type
terminals inside the electronics enclosure.
- The electronics shall include lightning/surge suppression
on the AC power input, and sensor.
D. OPTIONAL FEATURES FOR INSERTION IN SPECIFICATION AS
REQUIRED
- Have a power input of 220-240VAC 50/60Hz.
- Have a power input of 24VDC.
- Have 20 ft. (6 m) continuous shielded coaxial sensor
cable with waterproof, potted bond to the Sensor head.
- Include manufacturer's stainless steel Sensor Mounting
Clamp for specified pipe size.
- Have a thermostatically controlled enclosure heater
suitable to sustain the electronics without damage to
-40°F (-40°C).
E. MANUFACTURER
The flow switch shall be a Model MFS100 Microphone Flow Switch
as manufactured by Greyline Instruments Inc., and warranted
against defects in materials and workmanship for one year.